Baharun, Azhaili and Imran, Muhammad Syukri and Ibrahim, Siti Halipah and Abidin, Wan Azlan Wan Zainal
(2018)
Night Cooled Radiant Cooling Panel for Sustainable Building
Cooling Mode in Malaysia.
Journal of Construction in Developing Countries , 23 (1).
pp. 61-79.
ISSN 1823-6499
Abstract
Night air temperature in Malaysia is generally about 23°C and is a potential source
of heat sink to dissipate heat gain from a building. A thermal storage tank was used to store
a certain quantity of water and was passively cooled during the night using the pitched roof
as a heat exchanger to chill the water to as low as 22°C. The free cooling of water was then
used as a cooling medium to cool the modular radiant cooling panel during the day time
when the outdoor temperature exceeds 30°C. The experiment shows that the system was
able to maintain an indoor temperature of less than 28°C when the outdoor temperature
peaked to nearly 34°C while providing acceptable thermal comfort with certain controlled air
movement. The use of the hydronic radiant cooling panel with free night cooled water as its
coolant is proven to have signifcant energy saving potential of up to 85% while at the same
time provide an acceptable room thermal comfort which meets the international standard
criteria such as the American Society of Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE) Standard 55.
Actions (login required)
|
View Item |